Sprinkler System Design Requirements Form

Sprinkler System Design Requirements Form

ASRS Sprinkler System Design Specification Form

ASRS Sprinkler System Design Specification Form

Table 1. Determining Number of Sprinklers per Branch Line for Ceiling Sprinkler System Hydraulic Design

Number of Sprinklers in Ceiling Design Ceiling Sprinkler Type Maximum Ceiling Slope Ceiling Construction Type Ceiling Sprinkler On-Line Spacing, ft (m) Number of Sprinklers per Branch Line in Design Area
6 Extended Coverage 2 in 12 Any Any 3
6 Extended Coverage 4 in 12 Unobstructed Any See Equation 1
6 Extended Coverage 4 in 12 Obstructed Any See Equation 2
8 Extended Coverage 1 in 12 Any ≤ 12 (3.7) 4
8 Extended Coverage 1 in 12 Any > 12 (3.7) 3

Table 2. Hose Demand Design and Water Supply Duration

Reference: Page 19 of FM Global Property Loss Prevention Data Sheet 8-34

Ceiling Sprinkler Type Number of Sprinklers in the Ceiling Sprinkler System Design Hose Demand, gpm (L/min) Water Supply Duration, min
Standard-Coverage 12 or less 250 (950) 60
13 to 19 500 (1,900) 90
20 or more 500 (1,900) 120
Extended-Coverage 6 or less 250 (950) 60
7 to 9 500 (1,900) 90
10 or more 500 (1,900) 120

Table 3. Determining Which Ceiling Sprinkler Protection Table to Use for the Protection of Closed-Top Combustible Containers or Storage Trays

Reference: Page 21 of FM Global Property Loss Prevention Data Sheet 8-34

Material Handling Method Commodity Classification (No Open-Top Containers Permitted) Ceiling Sprinkler System Type Protection Table to Use
Directly on Supporting Rails Class 1 through Class 3 Wet 4
Dry 5
Class 4 and Cartoned Unexpanded Plastics Wet 6
Dry 7
Cartoned Expanded Plastics Wet 8
Dry 9
Uncartoned Unexpanded Plastics Wet 10
Dry 11
Uncartoned Expanded Plastics Wet 12
Dry 13
On Trays Class 1 through 4, Cartoned Plastics, and Uncartoned Unexpanded Plastics Wet 10
Dry 11
Uncartoned Expanded Plastics Wet 12
Dry 13

Table 4. Ceiling-Level Protection Guidelines on a Wet System for Class 1, 2, and 3 Commodities Stored Directly on the Supporting Rails of a Shuttle ASRS; No. of AS @ psi (bar)

Reference: Page 22 of FM Global Property Loss Prevention Data Sheet 8-34

Max. Ceiling Height, ft (m) Wet System, 160˚F (70˚C) Nominally Rated, Pendent Sprinklers Wet System, 160°F (70°C) Nominally Rated, Upright Sprinklers
Quick-Response Quick-Response
K11.2 (K160) K14.0 (K200) K16.8 (K240) K22.4 (K320) K25.2 (K360) K25.2EC (K360EC) K28.0 (K400) K33.6 (K480) K11.2 (K160) K14.0 (K200) K16.8 (K240) K25.2EC (K360EC)
10 (3.0) 12 @ 7 (0.5) 9 @ 7 (0.5) 9 @ 7 (0.5) 9 @ 20 (1.4) 9 @ 20 (1.4) 6 @ 20 (1.4) 9 @ 40 (2.8) 9 @ 55 (3.8) 12 @ 7 (0.5) 9 @ 7 (0.5) 9 @ 7 (0.5) 6 @ 20 (1.4)
20 (6.1) 12 @ 10 (0.7) 12 @ 7 (0.5) 12 @ 13 (0.9) 9 @ 20 (1.4) 9 @ 20 (1.4) 6 @ 20 (1.4) 9 @ 40 (2.8) 9 @ 55 (3.8) 12 @ 10 (0.7) 12 @ 7 (0.5) 12 @ 7 (0.5) 6 @ 20 (1.4)